1
00:00:00,000 --> 00:00:07,000
Welcome to the Windshield Chronicles, a mental sequence of operation.

2
00:00:07,000 --> 00:00:13,000
This episode brought to you by the Nextar Network and Nextech Academy.

3
00:00:13,000 --> 00:00:18,000
Visit nextarnetwork.com for more information.

4
00:00:22,000 --> 00:00:25,000
Hello everyone, thank you for joining Windshield Chronicles.

5
00:00:25,000 --> 00:00:30,000
We're spending some time today with Joe DeLong of Nextar and Nextech Academy.

6
00:00:30,000 --> 00:00:31,000
Joe, thanks for joining us.

7
00:00:31,000 --> 00:00:33,000
Thanks for having me, Clifton.

8
00:00:33,000 --> 00:00:37,000
Let's go through a mental sequence of operation for a gas furnace.

9
00:00:37,000 --> 00:00:42,000
So say we're heading out to a call for a no heat and let's pick on a basic furnace.

10
00:00:42,000 --> 00:00:46,000
Let's pick on, let's just say a Goodman single stage furnace.

11
00:00:46,000 --> 00:00:50,000
And walk through a mental sequence of operation for the entire wiring diagram

12
00:00:50,000 --> 00:00:54,000
so that we can prepare for this job before we get there.

13
00:00:54,000 --> 00:00:56,000
Absolutely sounds good.

14
00:00:56,000 --> 00:00:59,000
So in this situation, we're on our way to a call.

15
00:00:59,000 --> 00:01:00,000
We got a no heat.

16
00:01:00,000 --> 00:01:04,000
Clifton just said we got 80%, 80,000 BTU single stage Goodman.

17
00:01:04,000 --> 00:01:05,000
No heat.

18
00:01:05,000 --> 00:01:07,000
We arrive at the call.

19
00:01:07,000 --> 00:01:08,000
Filters clean.

20
00:01:08,000 --> 00:01:09,000
That's looking good.

21
00:01:09,000 --> 00:01:11,000
We're going to turn the thermostat on.

22
00:01:11,000 --> 00:01:17,000
We're not hearing anything happen downstairs when we go to the basement or get the furnace.

23
00:01:17,000 --> 00:01:23,000
So first thing we're going to do is we want to go down there and open up that bottom panel door.

24
00:01:23,000 --> 00:01:28,000
If we're looking at a furnace that's sitting vertical in a basement, for example.

25
00:01:28,000 --> 00:01:33,000
And when we open up that bottom panel door, we want to make sure our door switches closed.

26
00:01:33,000 --> 00:01:35,000
Blower compartment.

27
00:01:35,000 --> 00:01:36,000
Yeah, the blower compartment.

28
00:01:36,000 --> 00:01:40,000
Because it could be the upper door if we're in a counter flow position.

29
00:01:40,000 --> 00:01:41,000
Yes, that is correct.

30
00:01:41,000 --> 00:01:42,000
That is correct.

31
00:01:42,000 --> 00:01:46,000
So let's get the blower door open for that furnace.

32
00:01:46,000 --> 00:01:52,000
And you know, you're going to need to get some either some tape or you're going to need to get some like a magnet.

33
00:01:52,000 --> 00:01:58,000
The magnet switches are nice to make sure that door switches closed.

34
00:01:58,000 --> 00:02:03,000
But that's going to have to be in place in order for us to be checking power and voltage.

35
00:02:03,000 --> 00:02:10,000
So when we go through the sequence of operation, let's let's start by looking at our disconnect.

36
00:02:10,000 --> 00:02:14,000
So we have L1, we have ground and we have a neutral.

37
00:02:14,000 --> 00:02:18,000
OK, just to make sure everything's going good on the power side.

38
00:02:18,000 --> 00:02:25,000
It's never a bad idea to open up that disconnect and check for, you know, tight connections inside that disconnect box.

39
00:02:25,000 --> 00:02:28,000
Make sure you don't have any burnt or loose connections.

40
00:02:28,000 --> 00:02:35,000
And then leaving that disconnect box, we're going to go into the junction box of the actual gas furnace.

41
00:02:35,000 --> 00:02:40,000
So when we open that up, you're going to see a typically a black wire for your L1.

42
00:02:40,000 --> 00:02:45,000
You're going to see a ground coming in and you're going to see a neutral, which is typically white.

43
00:02:45,000 --> 00:02:51,000
And you're going to see some wire connections that the installer made inside that junction box.

44
00:02:51,000 --> 00:02:57,000
Now, what we're going to want to check for is obviously we want to see if we have power coming in.

45
00:02:57,000 --> 00:03:06,000
Now, one of the easiest ways to tell is if if if the board is OK, you're going to see some type of an indicator light on that circuit board.

46
00:03:06,000 --> 00:03:10,000
What we're going to want to do is following that wiring diagram.

47
00:03:10,000 --> 00:03:19,000
We're going to want that power wire is going to come from the junction box and it's going to go directly into our door switch door switches, just like a light switch.

48
00:03:19,000 --> 00:03:25,000
It's either open or closed. So if it's open, if that door switches open, we're not going to have any power going to our circuit board at all.

49
00:03:25,000 --> 00:03:30,000
Granted, we taped it or used a little magnetic switch to close that door switch.

50
00:03:30,000 --> 00:03:41,000
If everything's good there, that power wire is going to go directly into our circuit board and it's going to go to an L1 terminal on that board.

51
00:03:41,000 --> 00:03:51,000
And this is assuming that we have checked from ground to hot to make sure that we have proper voltage from neutral to hot that we have proper voltage.

52
00:03:51,000 --> 00:03:57,000
And I always like to verify between ground and neutral to make sure that we do not have any voltage between ground and neutral,

53
00:03:57,000 --> 00:04:02,000
which could show that we have a potentially open neutral back through our electrical circuit.

54
00:04:02,000 --> 00:04:13,000
That is 100% correct. And then what we want to do is we want to make sure that between L1 and ground that we have 120 volts AC.

55
00:04:13,000 --> 00:04:21,000
Also, if your neutral is is burnt or it is loose, that is also going to cause a voltage problem.

56
00:04:21,000 --> 00:04:33,000
Another thing that you want to keep in mind, it's it's pretty rare to happen in like a residential setting like this is you want to make sure you don't have any voltage fluctuations plus or minus 10%

57
00:04:33,000 --> 00:04:37,000
when we're looking at what our voltage is coming in.

58
00:04:37,000 --> 00:04:47,000
So when we follow our power wire coming into that board, that should be landing on what is typically an L1 terminal on your circuit board.

59
00:04:47,000 --> 00:04:59,000
That's going to be the same whether it's a two stage furnace, whether it's a variable speed, whether it's a PSC motor, 95% of the residential circuit boards that are out on the market.

60
00:04:59,000 --> 00:05:03,000
The power coming in is going to go to L1. Okay. Right.

61
00:05:03,000 --> 00:05:13,000
Then you're going to see another wire that is labeled either L1 XFMR or it's going to be XFMR line.

62
00:05:13,000 --> 00:05:21,000
And what that is, is you got to remember that a board is just simply a series of inputs and outputs.

63
00:05:21,000 --> 00:05:35,000
That's right. So if we are coming in and we're supplying that board with the 120 volts AC that it needs, we have to make sure that that board is supplying power, sufficient high voltage power to our transformer.

64
00:05:35,000 --> 00:05:42,000
Exactly. So what that means is from our L1 terminal between that and neutral, we should have 120 volts AC.

65
00:05:42,000 --> 00:05:57,000
Okay. Then when we look at the transformer terminal on that board, so from XFMR to neutral on the board, we also need to have 120 volts AC.

66
00:05:57,000 --> 00:06:05,000
So what that's telling me is that transformer is getting 120 volts from that input that's coming in from the power.

67
00:06:05,000 --> 00:06:07,000
Directly through the control board.

68
00:06:07,000 --> 00:06:28,000
Exactly. Directly through the control board. So if we are in a situation where we had 120 volts between L1 and neutral on the board, and we had zero volts between XFMR and neutral, that tells me that we have a bad board because the power is coming in, but we're not sending any of that power to our transformer.

69
00:06:28,000 --> 00:06:30,000
Exactly. It's not passing completely through the board.

70
00:06:30,000 --> 00:06:45,000
Exactly. So again, it's a series of inputs and outputs. So as long as we are getting power to that transformer between XFMR and neutral, that tells me the primary side of our transformer is getting voltage.

71
00:06:45,000 --> 00:06:47,000
Has sufficient voltage.

72
00:06:47,000 --> 00:06:48,000
Exactly.

73
00:06:48,000 --> 00:07:05,000
Now granted our transformer is good, and we don't have any issues with that. Then we have our low voltage side. So we're going to have 24 volts and we're going to have a common on the secondary side of our transformer.

74
00:07:05,000 --> 00:07:09,000
That's also going to have terminals on that board.

75
00:07:09,000 --> 00:07:15,000
And that should have 24 volts as long as the transformer is good.

76
00:07:15,000 --> 00:07:30,000
So if you walk up to a transformer, you don't see any LED lights or anything on that board. It's either a possibility that the fuse the low voltage fuse that's also on that board is either blown or that transformers bad.

77
00:07:30,000 --> 00:07:38,000
So that's another thing to keep in mind is nothing's going to work in here. If we don't have sufficient line voltage power coming in.

78
00:07:38,000 --> 00:07:50,000
That is also feeding the line voltage or primary side of our transformer. And then if the transformers good, we're going to be able to supply that low voltage side or the secondary side of our transformer.

79
00:07:50,000 --> 00:08:01,000
As long as those two things are good, and we don't have any low voltage shorts, we should be getting a diagnostic LED of some type on that board.

80
00:08:01,000 --> 00:08:11,000
Typically, it's like a on most Goodman's. It's just a standard red light. If you don't have a call for heat, nothing's going on. It's probably just going to be a steady red light on that board.

81
00:08:11,000 --> 00:08:25,000
Now, at this point, let's just assume that our low voltage is good on the on the transformer. We have sufficient power coming into the board. Our thermostat is telling us that there is a call for heat.

82
00:08:25,000 --> 00:08:47,000
We need to verify that there's call for heat. Okay. Now, with this particular board, the the system itself. And when I say the system, the board, the logic in that control board, the algorithm that's built into it is going to constantly be checking all of the limits within this system.

83
00:08:47,000 --> 00:09:05,000
When I say limits, we may have a auxiliary limit that's that's a low voltage limit that's attached to the blower assembly. There could be one there could be two of those. I've seen them where they have it on both sides of the back end of the or the front and the back of the blower assembly.

84
00:09:05,000 --> 00:09:29,000
Then you have your your main limit or your high limit switch that's going to be attached to the firebox the furnace. Then you're going to have your rollout switches. Those are going to be in place pressure switches the pressure switches the system's going to check to make sure that those pressure switches are open prior to a call for heat because of those pressure switches are closed.

85
00:09:29,000 --> 00:09:50,000
That's going to pop up an error code right off the bat. So the system is going through all of these different safeties within the circuit and constantly doing a check to make sure that those those limits and the safeties and the pressure switches and all of that are closed or open whichever their default is.

86
00:09:50,000 --> 00:10:07,000
And if that's all good, then you should be having a signal between common and W of 24 volts on that circuit board. What that's going to do is if everything's good to go there, it the circuit board.

87
00:10:07,000 --> 00:10:23,000
Once it checks all the safeties again, it's going to allow 120 volts to go to L1 and neutral for your induced draft motor terminal on the control board.

88
00:10:23,000 --> 00:10:41,000
If we follow it, you'll notice that the igniter well in this case the igniter has its own terminal but a lot of times on a single stage Goodman you will see the igniter and the induced draft motor are typically on a four pin.

89
00:10:41,000 --> 00:11:00,000
Molex and when you look at the molex you'll see two white wires two black wires. However, if you follow them typically one black wire is going to go to your igniter one black wire is going to go to your inducer and then you got your two neutrals one for each the igniter and the induced draft motor.

90
00:11:00,000 --> 00:11:11,000
So the next sequence of operation like I said is once we have all of our all of our limits and all of our pressure switches are closed the induced draft motor is going to fire up.

91
00:11:11,000 --> 00:11:31,000
And in order for that to happen again inputs and outputs on the circuit board we got power coming into the board all the safeties are closed. Then we're going to the circuit board is going to send 120 volts out of that molex plug from the circuit board straight to the induced draft motor the

92
00:11:31,000 --> 00:11:50,000
draft induced draft motor has to turn on. Now granted we have no issues going on with the induced draft motor no issues inside the flu our pressure switch that is normally open will now close with the pressure provided in that induced draft motor in the heat exchanger.

93
00:11:50,000 --> 00:11:51,000
Sure.

94
00:11:51,000 --> 00:12:05,000
Once that pressure switch closes. Okay that there's two things that have to happen at this point. Number one, our pressure switch has to close once that induced draft motor is running.

95
00:12:05,000 --> 00:12:07,000
Okay.

96
00:12:07,000 --> 00:12:26,000
If that is good. The other part that needs to happen is the safeties have to continue to be closed or open whatever their default is the safeties have to be operating properly, then the system will allow the ignition sequence to begin.

97
00:12:26,000 --> 00:12:42,000
And that's when we going back to that same for molex plug. We are going to be now provide the circuit board is now going to be providing 120 volts out of that molex plug directly to our hot surface igniter.

98
00:12:42,000 --> 00:12:43,000
Okay.

99
00:12:43,000 --> 00:12:59,000
So once that hot surface igniter is good. The next thing that's going to happen in that sequence is once our hot surface igniter lights up. The next part of the sequence is that gas valve is going to receive a 24 volt signal.

100
00:12:59,000 --> 00:13:02,000
Again, from that circuit board.

101
00:13:02,000 --> 00:13:16,000
Granted all the safeties are closed. It's going to send a 24 volt signal to that gas valve, allowing the gas valve to open. So then at that point, when we're following the sequence of operation that gas valve opens.

102
00:13:16,000 --> 00:13:36,000
Now we should have flame present going across our gas train across all of our burners going from the side where the igniter is traveling across our burners to the opposite side. Now we have to have flame rectification going.

103
00:13:36,000 --> 00:13:46,000
So this is another thing that's very common in the northern states. If you're familiar with working on a lot of gas furnaces, these flame sensors can get dirty.

104
00:13:46,000 --> 00:13:47,000
Okay.

105
00:13:47,000 --> 00:14:03,000
I want to say on average, and you can correct me if I'm wrong, Clifton, but I think on average, most systems need a minimum of 1.5 to 2 microamps of a flame sense signal in a gas furnace.

106
00:14:03,000 --> 00:14:16,000
When I build my flame rectification circuit, it's just a simple diode resistor circuit to duplicate that flame ratification. I set that at about 1.5 microamps and so far it's worked on pretty much every board that I've encountered.

107
00:14:16,000 --> 00:14:17,000
Perfect.

108
00:14:17,000 --> 00:14:33,000
And, and, you know, we can we can obviously discuss the flame ratification process and how to do all those checks in a separate podcast. I'm sure you probably already have, but I have seen it to where on some systems in the field before I clean that flame sensor.

109
00:14:33,000 --> 00:14:47,000
If I'm thinking it's a dirty flame sensor, by all means, verify, verify, verify. I have seen it where they're like 0.3, 0.5. They're just simply not, they're just too dirty.

110
00:14:47,000 --> 00:14:59,000
Now granted, so I'm going to go back to that sequence again. So granted, we are getting a good flame signal. That flame sensor is going to allow our gas valve to stay on.

111
00:14:59,000 --> 00:15:19,000
Okay, so that gas valve is going to continue to send gas. We got flame, flame sensor is sensing that flame. Now, while we're in this period right here, typically if we have our fan in the auto position, our blower motor is not turning on yet.

112
00:15:19,000 --> 00:15:35,000
So right now we're in what is called a heat on delay. Correct. Okay, now there is a heat on delay setting on our circuit board. These are going to be adjustable based on typically seconds.

113
00:15:35,000 --> 00:15:52,000
So 90 seconds, 120. It just depends on the manufacturer. It could be set in minutes. It's typically set in seconds. What that means is we want to allow our heat exchanger to heat up before we turn on that blower motor so we're not blowing cold air into our condition space.

114
00:15:52,000 --> 00:16:05,000
So after that heat on delay, let's just say that we had a heat on delay of 60 seconds. The burners are going once we have ignition and our flame sensor is has proven flame.

115
00:16:05,000 --> 00:16:27,000
We are going to allow those burners to stay lit for let's just say a period of 60 seconds. Once that that heat on delay ends. Now the next spot of what's going to be happening in our sequence and on that circuit board is now we need to be sending voltage to our blower motor.

116
00:16:27,000 --> 00:16:51,000
So typically on the blower motor. Now keep in mind in this scenario we're dealing with a PC motor standard three speed motor so we need to be checking for voltage or you should have voltage between the neutral terminal and whatever your heating speed tap is set on for that blower motor.

117
00:16:51,000 --> 00:17:06,000
So let's just say we have it on lows. Let's see in this case medium low. So we have an orange wire coming out of our blower motor that's going to the circuit board for the heating mode of operation.

118
00:17:06,000 --> 00:17:24,000
We need to have power going between neutral and that orange wire and that is going to be the voltage that we need to get that blower motor turn on. Now keep in mind. We're also assuming in this case that you have a good run capacitor for this

119
00:17:24,000 --> 00:17:37,000
PC blower motor. If that is the case and you have sufficient voltage the next part of the sequence of operation is that blower motor needs to turn on. Now real quick I'm just going to break for a second here.

120
00:17:37,000 --> 00:17:49,000
Clifton because you're something really important that I want to talk about here. So what I have seen from experience in the field that a lot of technicians have struggled with in the past is determining.

121
00:17:49,000 --> 00:18:18,000
Okay, this is a bad board or this is a bad blower motor. Right. And I have seen that that that problem right there or that confusion come up quite a few times. So one thing I want to make very certain here is one thing you want to make sure when you're trying to determine is this a bad circuit board or is this a bad blower motor is simply looking at the circuit board and checking for voltage between the neutral and the high voltage.

122
00:18:18,000 --> 00:18:29,000
Check between the neutral bank and when I say bank you're going to have a whole bunch of typically white wires all clustered together all clustered together on a neutral bank.

123
00:18:29,000 --> 00:18:47,000
Check between the actual wire that is connected to the neutral for the blower motor which is typically white, maybe another color though. Check between that and check between the heating connection speed tap on that board and verify

124
00:18:47,000 --> 00:18:50,000
that you have 120 volts.

125
00:18:50,000 --> 00:19:09,000
Okay, if everything's if everything's firing up on that entire system, and you got ignition and the heat on delay has ended, and you're not getting voltage between neutral and your speed tap for your blower motor.

126
00:19:09,000 --> 00:19:13,000
Typically that's going to signal to you that you have a bad control board.

127
00:19:13,000 --> 00:19:31,000
Now there's another step that I do in the field, when I'm trying to verify that as well, is you can also put in a jumper or something going from your line coming line voltage coming into your board and leave your neutral connected and you can actually

128
00:19:31,000 --> 00:19:38,000
get that blower speed tap and connect it to a line voltage source and see if the blower turns on.

129
00:19:38,000 --> 00:19:39,000
Sure.

130
00:19:39,000 --> 00:19:49,000
So that's just another bypassing the relay on the board, easy test you could do which bypasses the relay on the board. Sure, absolutely. So, so I just wanted to touch on that real quick.

131
00:19:49,000 --> 00:19:59,000
Absolutely. Just to verify that it's either your board or the motor. Now, going back to the sequence of operational let's assume everything's working again.

132
00:19:59,000 --> 00:20:19,000
The motor's running burners are on. Now at this point, we are going to be running the, the entire system until that thermostat satisfies. Now, another thing that the system is going to constantly be checking is checking for closed rollout switches

133
00:20:19,000 --> 00:20:31,000
or closed main limit switch. And if any of those things are off that's going to break the whole sequence of operation and typically give you an error code on that board.

134
00:20:31,000 --> 00:20:52,000
Now, once the whole system was to say the whole system goes through, and we reach the set temperature on that thermostat. The very first thing that's going to happen is the gas valve is going to open, which means we're no longer going to send a 24 volt signal to that

135
00:20:52,000 --> 00:21:03,000
gas valve. So the gas valve is going to open the induced draft motor is going to run for a little while in that purge cycle that's predetermined from the factory. Post purge.

136
00:21:03,000 --> 00:21:23,000
Yes. And then once that that happens, the blower motor will continue to run. So before we had a heat on delay now we have a heat off delay. So one of the things that we don't want to do is we don't want to shut off the gas valve and shut off the blower motor all at the same time.

137
00:21:23,000 --> 00:21:35,000
Because what's typically going to happen in that case is your heat exchanger is still very hot. And we don't want to shut everything off because then what's going to happen is we're probably going to open up a main limit switch.

138
00:21:35,000 --> 00:22:01,000
Right. If we shut everything off at all at once. So the heat off delay 90 120 150 seconds, whatever that setting is on the board, which typically is adjustable. What that means is that the gas valve is going to shut off, we're no longer burning at the burners, and that blower motor is going to continue to run to get that heat exchanger cool down and that also provides

139
00:22:01,000 --> 00:22:07,000
hot air to go into the condition space after the burners shut down.

140
00:22:07,000 --> 00:22:15,000
Once that heat off delay ends, then the last very last step of that is the blower motor will then shut down.

141
00:22:15,000 --> 00:22:23,000
And granted everything's still working again that circuit boards can sit there waiting for the next call.

142
00:22:23,000 --> 00:22:27,000
All right, Joe DeLong, thank you so much for joining us and we appreciate your time today.

143
00:22:27,000 --> 00:22:35,000
Thank you.

