1
00:00:00,000 --> 00:00:05,900
Welcome back to Teaching the Unteachables, where we dive into teaching and learning

2
00:00:05,900 --> 00:00:11,080
methodologies for professionals like you. This episode brought to you by

3
00:00:11,080 --> 00:00:16,080
Stanfield Training Solutions, your source for HVACR training solutions.

4
00:00:16,080 --> 00:00:22,480
Learn more at hvacrfundamentals.com.

5
00:00:23,520 --> 00:00:28,100
Well hello everyone, thank you for joining Did You Know? the ESCO HVAC

6
00:00:28,100 --> 00:00:33,200
podcast. So today we're joined by esteemed author Carter Stanfield. How are

7
00:00:33,200 --> 00:00:39,440
you sir? I'm doing great. Author of Fundamentals of HVACR, published by

8
00:00:39,440 --> 00:00:46,120
Pearson. Carter is very involved with education as well as authoring in the

9
00:00:46,120 --> 00:00:51,800
industry and we both have a passion for understanding where things come from. I

10
00:00:51,800 --> 00:00:54,880
always say that you can't know where you're going unless you know where you

11
00:00:54,880 --> 00:01:00,560
came from and that's very true when we start talking about this A2L transition.

12
00:01:00,560 --> 00:01:05,680
And really it's a, when we look at it, it's more about the low GWP transition

13
00:01:05,680 --> 00:01:09,700
because yes we're seeing the A2L transition but we're also seeing an A3

14
00:01:09,700 --> 00:01:14,440
transition as well. And so today we're going to spend some time talking about

15
00:01:14,440 --> 00:01:18,680
where the standards come from, particularly ASHRAE Standard 15 and

16
00:01:18,680 --> 00:01:24,400
Standard 34. And Mr. Stanfield has spent a lot of time breaking these down and

17
00:01:24,400 --> 00:01:30,280
Carter if you could help us understand a little bit about this transition and why

18
00:01:30,280 --> 00:01:37,680
we're doing the things that we're doing. Sure. So I like to emphasize it you

19
00:01:37,680 --> 00:01:46,880
mentioned knowing where things come from. I like to look at the the original

20
00:01:46,880 --> 00:01:54,380
documents to things. So while I love presentations given by people, I like to

21
00:01:54,380 --> 00:02:00,840
see the original documents where their information came from. Absolutely. So when

22
00:02:00,840 --> 00:02:09,480
it comes to refrigerant, ASHRAE 34 is the standard that really all codes and

23
00:02:09,480 --> 00:02:20,080
even the UL qualification refer to. So ASHRAE 34 is the document that gives the

24
00:02:20,080 --> 00:02:25,960
refrigerants their numbers and also it's where our safety standard comes

25
00:02:25,960 --> 00:02:32,360
from. So the A1 through B3 and all the numbers and A2L, all that comes from

26
00:02:32,360 --> 00:02:38,140
ASHRAE 34. So I like to be able to refer to the original document and see

27
00:02:38,140 --> 00:02:44,080
exactly how they define things. This is particularly important now as we try to

28
00:02:44,080 --> 00:02:50,760
understand what an A2L is versus say an A1. Yeah absolutely. A lot of people

29
00:02:50,760 --> 00:02:54,920
don't realize you know where these transitions come from. We get a lot of

30
00:02:54,920 --> 00:03:00,320
calls at the ESCO office and sometimes complaints about these transitions going

31
00:03:00,320 --> 00:03:04,120
why are the manufacturers of equipment doing this to us again? And it's

32
00:03:04,120 --> 00:03:08,840
actually never been the manufacturers of equipment. Like when we talk about this

33
00:03:08,840 --> 00:03:14,160
A2L transition, we're really talking about the HFC phase down that came

34
00:03:14,160 --> 00:03:17,120
through in two different ways. It came through with a Kigali amendment to the

35
00:03:17,120 --> 00:03:22,480
Montreal Protocol as well as a portion of the AIM Act. So not only do we have an

36
00:03:22,480 --> 00:03:26,200
act of Congress but we have an international treaty that is phasing

37
00:03:26,200 --> 00:03:31,640
down the use of hydrofluorocarbon refrigerants. And so in doing that we

38
00:03:31,640 --> 00:03:34,920
have to look at what are the next generations of refrigerants, how do we

39
00:03:34,920 --> 00:03:39,200
safely handle them, and what other refrigerants could we see going forward?

40
00:03:39,200 --> 00:03:43,240
Because this is just one step of a variety of transitions that I'm sure

41
00:03:43,240 --> 00:03:48,800
we're going to see. Now many of us seen the CFC phase out. We've seen the H CFC

42
00:03:48,800 --> 00:03:54,560
phase out. We're now in the HFC phase down and remember it's not a complete

43
00:03:54,560 --> 00:04:02,200
phase out but it is a phase down by 85% by 2036. So what that means is we have to

44
00:04:02,200 --> 00:04:06,920
start looking at what other refrigerants do we have to work with. And you know

45
00:04:06,920 --> 00:04:10,920
we'll take chemists like Dr. Chuck over at Comoros who says that the periodic table

46
00:04:10,920 --> 00:04:16,400
doesn't really grow. We just have to reuse the elements that we have. And in

47
00:04:16,400 --> 00:04:21,080
doing that unfortunately we we end up with refrigerants that will have some

48
00:04:21,080 --> 00:04:25,240
mildly flammable and even highly flammable characteristics going forward.

49
00:04:25,240 --> 00:04:29,720
But then like how do you work with them? How do the manufacturers design the

50
00:04:29,720 --> 00:04:33,440
equipment? How did the tool manufacturers relook at and sometimes

51
00:04:33,440 --> 00:04:37,560
redesign their tools? There's a lot of safety that goes into that and we have

52
00:04:37,560 --> 00:04:42,640
to have something to start with. And that's really where ASHRAE 34 comes into

53
00:04:42,640 --> 00:04:49,680
play. Yeah ASHRAE has been doing refrigerant safety for quite a while and

54
00:04:49,680 --> 00:04:56,320
again it is really the backbone of most of the refrigerant safety standards.

55
00:04:56,320 --> 00:05:06,240
ASHRAE 15 which is also widely documented is used in many codes and

56
00:05:06,240 --> 00:05:13,040
essentially all the rules for refrigerant mechanical rooms, mechanical

57
00:05:13,040 --> 00:05:18,920
rooms and refrigerant systems in them basically refer back to ASHRAE 15. The

58
00:05:18,920 --> 00:05:24,040
issue that we've had with ASHRAE 15 is that it's primarily a commercial standard.

59
00:05:24,040 --> 00:05:32,760
Right. People don't have mechanical rooms in their houses. So ASHRAE 15.2

60
00:05:32,760 --> 00:05:41,800
covers low-rise residential structures and specifically really lays out all

61
00:05:41,800 --> 00:05:48,600
the safety requirements for installing and servicing A2L systems. It does also

62
00:05:48,600 --> 00:05:57,000
cover A1 systems but its primary purpose for being has to do with installation

63
00:05:57,000 --> 00:06:04,720
and service of A2L systems. And it was developed sort of in parallel with the

64
00:06:04,720 --> 00:06:16,640
UL, the number? 60 335-3-40. Okay thank you. Absolutely. And that UL standard

65
00:06:16,640 --> 00:06:23,560
actually came from an IEC standard of the same name, the same number. That's

66
00:06:23,560 --> 00:06:26,600
why they came up with that number because they harmonized the standard

67
00:06:26,600 --> 00:06:33,040
with the IEC standard. There's something that you know when we talk about

68
00:06:33,040 --> 00:06:38,160
worrying about global warming and getting rid of our high global warming

69
00:06:38,160 --> 00:06:44,040
refrigerants, this is not just a US thing. This is an international thing. That's

70
00:06:44,040 --> 00:06:49,040
right. The reason it's important to manufacturers is that we don't want to

71
00:06:49,040 --> 00:06:54,320
be on an island. We don't want to be the only people in the world using a

72
00:06:54,320 --> 00:06:58,440
particular type of refrigerant or having particular kinds of systems. The

73
00:06:58,440 --> 00:07:03,720
manufacturers both of the refrigerant and equipment want to be international.

74
00:07:03,720 --> 00:07:07,200
They want their products to be able want to be able to sell their products

75
00:07:07,200 --> 00:07:16,360
someplace besides the United States. So that gives some impetus. It's not just

76
00:07:16,360 --> 00:07:24,720
the government. There's also you know financial and industrial things

77
00:07:24,720 --> 00:07:30,400
at play here. And again it's an international movement. So it's not

78
00:07:30,400 --> 00:07:34,880
something that our government could just say okay well we don't want to do this

79
00:07:34,880 --> 00:07:39,360
anymore because we don't believe in it. We'd be bucking the whole world and

80
00:07:39,360 --> 00:07:45,880
basically it's sort of like isolationism. When we start talking about the the

81
00:07:45,880 --> 00:07:49,600
three different levels of mitigation what we're really talking about is the

82
00:07:49,600 --> 00:07:53,520
refrigerant concentration levels based on the flammability of the refrigerant.

83
00:07:53,520 --> 00:07:57,360
And when we start breaking down those refrigerants, so we started in ASHRAE 34

84
00:07:57,360 --> 00:08:02,520
to see what those flammable characteristics are, and then in 15-2 we

85
00:08:02,520 --> 00:08:05,880
can actually look at well when does that mitigation come into play because these

86
00:08:05,880 --> 00:08:09,960
smaller systems under four pounds and that's a rough estimate based on the

87
00:08:09,960 --> 00:08:14,080
refrigerant itself, under four pounds in these residential systems they actually

88
00:08:14,080 --> 00:08:20,800
don't even have mitigation. But once we reach that potential for combustion we

89
00:08:20,800 --> 00:08:24,960
actually we start adding mitigation to it. And so what we're going to see in

90
00:08:24,960 --> 00:08:29,400
particular residential systems is mitigation controls which is going to

91
00:08:29,400 --> 00:08:33,920
add a refrigerant leak detection sensor and a control to be able to mitigate

92
00:08:33,920 --> 00:08:44,040
those gases in the event of an actual significant leak. Yeah so on the the

93
00:08:44,040 --> 00:08:55,360
mitigation levels the UL standard and also the ASHRAE 15.2 refer to levels that

94
00:08:55,360 --> 00:09:03,320
charge levels they call M1, M2, and M3. I believe the M stands for mass. That

95
00:09:03,320 --> 00:09:09,480
makes sense. You know I haven't verified that with anybody. I'm just trying to

96
00:09:09,480 --> 00:09:14,920
come up with some reason why they use that. And then when they talk about the

97
00:09:14,920 --> 00:09:21,680
maximum charge and that sort of thing they also use M. But anyway M1 is six

98
00:09:21,680 --> 00:09:27,680
times the lower flammability limit, M2 is 52 times the lower flammability limit,

99
00:09:27,680 --> 00:09:34,880
and M3 is 260 times the lower flammability limit. So the weight amount

100
00:09:34,880 --> 00:09:39,040
varies with refrigerant because it depends on the refrigerant's density and

101
00:09:39,040 --> 00:09:43,920
the lower flammability limit of the refrigerant. Right. And it does it's it's

102
00:09:43,920 --> 00:09:49,080
just under four pounds for R32 and honestly I don't know right off the top

103
00:09:49,080 --> 00:09:58,080
of my head what it is for 454B. But it's in that same range. And to get a

104
00:09:58,080 --> 00:10:03,400
perspective on this I looked up I thought about P-TAC units. Yeah. And I

105
00:10:03,400 --> 00:10:10,240
looked up a Friedrich P-TAC unit of 12,000 BTUs and their charge was 1.8

106
00:10:10,240 --> 00:10:17,520
pounds of R32. So well under this four pounds. Yeah. Meaning that those units

107
00:10:17,520 --> 00:10:23,200
and say window units like you'd buy your big box store don't require any kind of

108
00:10:23,200 --> 00:10:30,000
special mitigation. When you go between M1 six times lower flammability limit up

109
00:10:30,000 --> 00:10:35,280
to M2 52 times a lower flammability limit you do require mitigation. And

110
00:10:35,280 --> 00:10:43,200
there's lots of ifs, ands, and buts, lots of different things that alter what the

111
00:10:43,200 --> 00:10:48,880
what mitigation is required. So that gets kind of detailed. And then there's

112
00:10:48,880 --> 00:10:57,240
more mitigation required between M2 and M3. And at M3 the 262 times of lower

113
00:10:57,240 --> 00:11:05,440
flammability limit basically that's outside of the UL standard. So that would

114
00:11:05,440 --> 00:11:11,040
require a whole different document. Exactly. And that's going to be large

115
00:11:11,040 --> 00:11:14,760
quantities of refrigerant large systems. Probably the only time we're going to

116
00:11:14,760 --> 00:11:19,920
see that is going to be in large VRV VRF installations. And it really comes down

117
00:11:19,920 --> 00:11:23,920
to once we get to that point we're going to add additional controls like pump

118
00:11:23,920 --> 00:11:30,320
down solenoids and ways to be able to do additional isolation of the refrigerant

119
00:11:30,320 --> 00:11:40,280
itself. Yeah. The again the mitigation varies a lot depending on the quantity

120
00:11:40,280 --> 00:11:46,520
of refrigerant and also where the system is applied. That's the only thing about

121
00:11:46,520 --> 00:11:54,080
standard 15. The requirements for what you're allowed to do and what you're

122
00:11:54,080 --> 00:12:01,040
required to do vary based really on three things. The occupancy, that's the

123
00:12:01,040 --> 00:12:12,720
building, the refrigerant, and oh the system. Oh yeah. Okay. Yeah. So I'll start

124
00:12:12,720 --> 00:12:19,040
from here. The mitigation varies depending on the type of occupancy.

125
00:12:19,040 --> 00:12:23,960
That's the type of building it is. The type of system, the type of refrigeration

126
00:12:23,960 --> 00:12:31,480
system, and the refrigerant classification. So when we talk about occupancy we're

127
00:12:31,480 --> 00:12:38,600
talking about say institutional would be hospitals and things where you have

128
00:12:38,600 --> 00:12:45,360
people that cannot easily move. Be relocated. That getting everybody out is

129
00:12:45,360 --> 00:12:51,880
going to be a chore. Sure. And then when you talk about systems they've got

130
00:12:51,880 --> 00:12:56,720
several different kinds of systems but it really comes down to whether

131
00:12:56,720 --> 00:13:02,320
something is a high probability or low probability system. Now by high

132
00:13:02,320 --> 00:13:09,600
probability they're talking about the possibility or probability of refrigerant

133
00:13:09,600 --> 00:13:15,480
getting in the airstream in the building if there's a leak. So in our typical

134
00:13:15,480 --> 00:13:20,080
direct expansion systems are all high probability systems because refrigerants

135
00:13:20,080 --> 00:13:25,880
in the coil that the air blows over. Exactly. In the space. Yeah. So an example

136
00:13:25,880 --> 00:13:30,280
of a low probability system would be say like a chiller where the refrigerant

137
00:13:30,280 --> 00:13:34,000
cools water and then the water is pumped around. Even if you did have a leak the

138
00:13:34,000 --> 00:13:39,680
chance of the refrigerant getting in the air is extreme. Minimal. Yeah. So the

139
00:13:39,680 --> 00:13:46,620
standards are different for those. So until recently the standard ASHRAE 15

140
00:13:46,620 --> 00:13:52,840
would not allow flammable refrigerant in a high probability system. So the

141
00:13:52,840 --> 00:14:01,320
first allowance of any kind of flammable refrigerant in a high probability

142
00:14:01,320 --> 00:14:09,720
system came about in the 2019 revision of the ASHRAE standard 15. The ASHRAE

143
00:14:09,720 --> 00:14:18,600
standard 34 recognized A2L refrigerants in 2016 but it was not until 2019 that

144
00:14:18,600 --> 00:14:26,800
they said in standard 15 that you could use A2L systems in a high probability

145
00:14:26,800 --> 00:14:33,480
system and there's again lots of parameters. So that's where we get into

146
00:14:33,480 --> 00:14:38,400
the mitigation and the amount of mitigation and the type of mitigation

147
00:14:38,400 --> 00:14:45,720
varies based on the quantity of refrigerant and the application. Yeah a

148
00:14:45,720 --> 00:14:49,760
lot of people don't realize that like you'd mentioned before a lot of our

149
00:14:49,760 --> 00:14:54,000
window units and P-TECH units have already made the transition to A2L

150
00:14:54,000 --> 00:14:58,680
refrigerants. Pretty much any window air conditioner you buy right now has R32 in

151
00:14:58,680 --> 00:15:04,000
it. Same way with the P-TECHs. Yeah you'd have a hard time actually finding a

152
00:15:04,000 --> 00:15:09,600
window unit that doesn't have 32 in it. Exactly and because of that charge limit

153
00:15:09,600 --> 00:15:13,600
of around four pounds most of those window units have a pound or under of

154
00:15:13,600 --> 00:15:17,520
refrigerant so they have no additional requirements for mitigation. In our

155
00:15:17,520 --> 00:15:21,680
residential and light commercial applications we're going to see factory

156
00:15:21,680 --> 00:15:26,800
leak refrigerant detection sensors as well as the controls that go with them.

157
00:15:26,800 --> 00:15:31,760
If it is a non-communicating system it's going to have a independent control

158
00:15:31,760 --> 00:15:35,560
module which is basically going to be connected between the thermostat and the

159
00:15:35,560 --> 00:15:40,000
indoor unit so that in the case of a detection we're actually going to go into

160
00:15:40,000 --> 00:15:43,960
a mitigation state which is going to turn off the outdoor unit. It would turn

161
00:15:43,960 --> 00:15:48,280
off any heat source inside whether it was electric furnace or whether it was a gas

162
00:15:48,280 --> 00:15:52,240
furnace it would actually turn off those ignition sources and turn on the blower

163
00:15:52,240 --> 00:15:56,560
to dissipate those gases. If it's a communicating system most of our

164
00:15:56,560 --> 00:16:01,160
manufacturers have incorporated that control into the indoor board and so

165
00:16:01,160 --> 00:16:04,080
literally it's a matter of just connecting the sensor that comes with

166
00:16:04,080 --> 00:16:09,040
the coil down to the control board of the indoor unit and now it's actually

167
00:16:09,040 --> 00:16:17,200
ready for a mitigation capable system. Yeah I didn't know that that's that's a

168
00:16:17,200 --> 00:16:22,800
good information. Yeah I've spent a lot of time on how we're actually utilizing

169
00:16:22,800 --> 00:16:28,080
the mitigation controls so if it is a non-communicating system you're going to

170
00:16:28,080 --> 00:16:34,240
have an additional control board. If it is a communicating system the the same

171
00:16:34,240 --> 00:16:38,640
refrigerant detection sensor is just going to be plugged into the primary

172
00:16:38,640 --> 00:16:42,440
control board of that indoor unit. At least that's what I've seen with the

173
00:16:42,440 --> 00:16:46,840
manufacturers that I've went through so far and then when we get into our VRV

174
00:16:46,840 --> 00:16:51,960
VRF because it's already a communicating board on the indoor unit that is able

175
00:16:51,960 --> 00:16:56,040
to communicate to the outdoor we're just adding the additional refrigerant

176
00:16:56,040 --> 00:17:00,480
detection sensor and it plugs directly into the control board. So as our systems

177
00:17:00,480 --> 00:17:04,960
make the transition it's going to be a little bit of a learning curve

178
00:17:04,960 --> 00:17:09,600
understanding what that installation looks like and in the installation

179
00:17:09,600 --> 00:17:13,320
manuals that I've seen for our residential like commercial split

180
00:17:13,320 --> 00:17:17,760
systems they actually give you all of the dimensions for if this system is

181
00:17:17,760 --> 00:17:23,280
installed in this cubic amount of space mitigation is required and here's how

182
00:17:23,280 --> 00:17:28,600
you make the connections. So it's pretty basic but it is definitely a transition

183
00:17:28,600 --> 00:17:32,760
that we're going to be making and it takes a little education and so the

184
00:17:32,760 --> 00:17:37,280
whole conversation today was where does that education come from. Most of it

185
00:17:37,280 --> 00:17:43,760
comes from standard 15 and standard 34. It's interesting that you mentioned the

186
00:17:43,760 --> 00:17:50,960
room volume it is one of the kind of significant changes. There the

187
00:17:50,960 --> 00:17:58,720
manufacturers part of the UL standard is they have to with the equipment when

188
00:17:58,720 --> 00:18:05,360
it's checked for the UL requirement they have to actually supply the

189
00:18:05,360 --> 00:18:12,080
installation instructions that they're going to package with the equipment and

190
00:18:12,080 --> 00:18:21,400
they have to provide tables rather than just formulas for technicians to be able

191
00:18:21,400 --> 00:18:28,560
to determine whether or not a particular piece of equipment will safely work in a

192
00:18:28,560 --> 00:18:33,620
space and they do that two ways. One of these they give they tell you equipment

193
00:18:33,620 --> 00:18:39,760
with this charge can go in a space no smaller than and they give you you know

194
00:18:39,760 --> 00:18:45,320
the volume and the other is they say it will if your space is this size the

195
00:18:45,320 --> 00:18:51,760
maximum charge you can have is and they give you a number. You're also going to

196
00:18:51,760 --> 00:18:59,400
be required to calculate total charge meaning in a split system or a many

197
00:18:59,400 --> 00:19:07,240
split system adding charge for the for the line set. Now of course that's not

198
00:19:07,240 --> 00:19:16,600
that new but now it's a really legal requirement and something that a lot of

199
00:19:16,600 --> 00:19:23,760
speakers have mentioned in their A2L presentations is a lot of behaviors and

200
00:19:23,760 --> 00:19:31,240
procedures that have been best practice are now required practice if you want to

201
00:19:31,240 --> 00:19:37,480
do it safely. Exactly so that's all that's a little bit of education doing

202
00:19:37,480 --> 00:19:41,760
best practices are going to get you through a lot of the hurdles otherwise

203
00:19:41,760 --> 00:19:46,120
your installation manuals and training from your manufacturers and industry

204
00:19:46,120 --> 00:19:51,800
partners like all of us are here to help educate you and keep you current. So

205
00:19:51,800 --> 00:19:55,600
Carter if you're looking for more information where are some ways that

206
00:19:55,600 --> 00:20:04,440
people can locate Fundamentals of HVACR and Carter Stanfield? So I have a blog

207
00:20:04,440 --> 00:20:17,120
hvacrfundamentals.logspot.com and I have a website hvacrfundamentals.com

208
00:20:17,120 --> 00:20:24,440
and then if you you can also google Stanfield training solutions and I

209
00:20:24,440 --> 00:20:32,520
believe my website will come up. Also you can go to Pearson. Pearson has a website for

210
00:20:32,520 --> 00:20:40,320
the book so you can google the book title Fundamentals of HVACR and you

211
00:20:40,320 --> 00:20:46,600
should be able to find that Pearson website. Fantastic Mr. Stanfield we sure

212
00:20:46,600 --> 00:20:54,840
appreciate you joining us today. Thank you very much.

