1
00:00:00,000 --> 00:00:07,360
Welcome to the Windshield Chronicles, a mental sequence of operation.

2
00:00:07,360 --> 00:00:12,900
Always refer to your OEM installation and service manuals, but this is a guide on how

3
00:00:12,900 --> 00:00:19,760
5 volt DC communicating systems function and how to troubleshoot them in Daikin equipment

4
00:00:19,760 --> 00:00:20,760

5
00:00:20,760 --> 00:00:27,240
All right, everyone, thank you for joining us on Did You Know?, the ESCO HVAC podcast.

6
00:00:27,240 --> 00:00:32,720
So as part of our Windshield Chronicles, we're going to do a mental sequence of operation

7
00:00:32,720 --> 00:00:35,000
of a communicating system.

8
00:00:35,000 --> 00:00:40,520
In particularly, we're going to talk about the Daikin communicating system that's used

9
00:00:40,520 --> 00:00:43,440
in the residential unitary products.

10
00:00:43,440 --> 00:00:48,880
So when we're looking at a Daikin, this actually falls into play for some of the earlier Goodman

11
00:00:48,880 --> 00:00:53,640
& Manna communicating systems before they went to Comfort Bridge, but it also applies

12
00:00:53,640 --> 00:00:58,200
to the communicating that is going from the indoor to the outdoor, even on the Comfort

13
00:00:58,200 --> 00:00:59,640
Bridge system.

14
00:00:59,640 --> 00:01:06,040
So when we look at the Daikin, the Daikin is using the 5 volt DC communicating platform

15
00:01:06,040 --> 00:01:08,520
that is very common in the industry.

16
00:01:08,520 --> 00:01:12,720
There's other manufacturers that use this same protocol, but we're going to focus on

17
00:01:12,720 --> 00:01:16,780
this Daikin one in particularly, just so you can understand how it's functioning.

18
00:01:16,780 --> 00:01:23,000
So with that communicating system, so say we're working on like a Daikin Fit or any of

19
00:01:23,000 --> 00:01:30,160
the Daikin communicating systems, you're going to have four wires going between the thermostat

20
00:01:30,160 --> 00:01:34,900
and the indoor unit, whether it's air handler or gas furnace.

21
00:01:34,900 --> 00:01:40,760
We're going to have two wires that are going to be a part of the communication network,

22
00:01:40,760 --> 00:01:43,880
and that is number one and number two.

23
00:01:43,880 --> 00:01:49,600
But we also have R and C. Sound familiar, Ty?

24
00:01:49,600 --> 00:01:50,600
Very familiar.

25
00:01:50,600 --> 00:01:55,840
I mean, what would you assume would be on a R and C connection, even if it wasn't a

26
00:01:55,840 --> 00:01:56,840
communicating system?

27
00:01:56,840 --> 00:02:04,000
That's our 24 volt R and C. It's alternating current, 24 volt low voltage back and forth.

28
00:02:04,000 --> 00:02:05,000
Exactly.

29
00:02:05,000 --> 00:02:12,080
And so on this four wire connection, we actually have AC voltage as well as DC voltage.

30
00:02:12,080 --> 00:02:16,620
So from our thermostat, the Daikin communicating thermostat to the indoor unit and from the

31
00:02:16,620 --> 00:02:22,480
indoor unit to the outdoor unit, we are typically only going to use the two wire going outside,

32
00:02:22,480 --> 00:02:25,120
but I have seen applications that use those four.

33
00:02:25,120 --> 00:02:31,520
So if we think about this, let's say that I have my communicating indoor unit, my communicating

34
00:02:31,520 --> 00:02:36,200
thermostat and a communicating outdoor, and I only have two wires going to the outdoor

35
00:02:36,200 --> 00:02:37,520
unit.

36
00:02:37,520 --> 00:02:41,120
And because it would have been on a communicating system, that would have been at least a two

37
00:02:41,120 --> 00:02:44,500
stage communicating, it's probably going to be an inverter.

38
00:02:44,500 --> 00:02:49,560
Do I need 24 volts AC for the control board outside, Ty?

39
00:02:49,560 --> 00:02:53,000
Well, that would be depending on what the manufacturer wanted.

40
00:02:53,000 --> 00:02:55,400
The manufacturer wants that then absolutely.

41
00:02:55,400 --> 00:02:59,360
And if they didn't want that, then I figured those engineers have designed it to where

42
00:02:59,360 --> 00:03:03,440
they are already sealing the high voltage to get that, get that dropped down for their

43
00:03:03,440 --> 00:03:04,920
controls as needed.

44
00:03:04,920 --> 00:03:05,920
Exactly.

45
00:03:05,920 --> 00:03:10,760
So what they typically will do if I only have my two wires going to the outdoor unit, that

46
00:03:10,760 --> 00:03:15,660
is my DC communicating number one and number two.

47
00:03:15,660 --> 00:03:20,120
And so if it was like a two stage unit, they simply have you put the factory transformer

48
00:03:20,120 --> 00:03:24,920
or it's already supplied with a factory transformer on the outdoor unit.

49
00:03:24,920 --> 00:03:30,020
And so we do not want to connect the R and C from the outdoor unit to the indoor unit

50
00:03:30,020 --> 00:03:34,600
if I have a transformer out there, because then our AC voltages would be doing what?

51
00:03:34,600 --> 00:03:35,920
They'll be fighting each other.

52
00:03:35,920 --> 00:03:37,720
They'll be out of phase.

53
00:03:37,720 --> 00:03:38,820
Exactly.

54
00:03:38,820 --> 00:03:44,320
So what we do is if we have a transformer outdoor, that is supplying power to the outdoor

55
00:03:44,320 --> 00:03:45,320
unit.

56
00:03:45,320 --> 00:03:47,880
So we do not need AC voltage outside.

57
00:03:47,880 --> 00:03:51,780
And if it's an inverter, it's doing that in the control board itself.

58
00:03:51,780 --> 00:03:58,000
So the power supply of the board, the inverter board is managing the entire outdoor unit.

59
00:03:58,000 --> 00:04:01,320
So all it needs to do is communicate what are we doing?

60
00:04:01,320 --> 00:04:02,320
Are we running in heating?

61
00:04:02,320 --> 00:04:03,980
Are we running in cooling?

62
00:04:03,980 --> 00:04:05,680
And so how does it do that?

63
00:04:05,680 --> 00:04:12,040
Well, it's actually a very common process, not just in our industry, but in many communicating

64
00:04:12,040 --> 00:04:13,200
networks.

65
00:04:13,200 --> 00:04:18,040
So it's part of the RS-485 communicating system that's been around for decades.

66
00:04:18,040 --> 00:04:19,640
We use it for telephones.

67
00:04:19,640 --> 00:04:21,860
We use it for computer communications.

68
00:04:21,860 --> 00:04:24,040
We use it for a lot of things.

69
00:04:24,040 --> 00:04:33,480
And so what we do is we create a positive and a negative pathway in reference to ground.

70
00:04:33,480 --> 00:04:36,920
And this is where a lot of technicians, this is where a lot of people get caught up when

71
00:04:36,920 --> 00:04:41,120
we're thinking about the sequence of operation of a communicating system.

72
00:04:41,120 --> 00:04:49,920
If I have a positive and I have a negative, but it's in reference to ground, well, what

73
00:04:49,920 --> 00:04:54,160
do I normally do with the common side of an AC transformer tie?

74
00:04:54,160 --> 00:04:58,480
Well, half of the industry grounds that and the other half does not.

75
00:04:58,480 --> 00:04:59,440
Exactly.

76
00:04:59,440 --> 00:05:03,720
So with this particular system, you're going to find all of these transformers are going

77
00:05:03,720 --> 00:05:09,020
to be grounded so that common is a reference to ground.

78
00:05:09,020 --> 00:05:16,960
And so with that DC voltage, what we actually do is we separate out the signals in reference

79
00:05:16,960 --> 00:05:18,540
to ground.

80
00:05:18,540 --> 00:05:25,140
So we reduce the voltage down to five volts and then we put it in reference to ground.

81
00:05:25,140 --> 00:05:35,000
And so by using diodes and by using resistors, we can actually create a five volt DC pathway.

82
00:05:35,000 --> 00:05:37,200
So that's the bandwidth.

83
00:05:37,200 --> 00:05:44,280
And because we are now putting it into reference to ground, we can shift that ground from center

84
00:05:44,280 --> 00:05:46,360
just a little bit.

85
00:05:46,360 --> 00:05:51,120
And so that we have more voltage going to the positive side than what we have going

86
00:05:51,120 --> 00:05:54,400
to the negative side of our bandwidth.

87
00:05:54,400 --> 00:06:01,440
And so as technicians, it's a little bit different to think about this DC voltage.

88
00:06:01,440 --> 00:06:05,400
But when we think about it in reference to ground, it starts simplifying it.

89
00:06:05,400 --> 00:06:11,260
So with that DC, remember, most of our power supply is starting at that indoor unit.

90
00:06:11,260 --> 00:06:15,800
If I disconnect the wires at the indoor unit, whether it's a gas furnace or an air handler,

91
00:06:15,800 --> 00:06:24,800
when I put my meter on volts DC, I can now look for my five volts, but because it is

92
00:06:24,800 --> 00:06:30,560
in reference to ground and we have a negative voltage and we have a positive voltage, it's

93
00:06:30,560 --> 00:06:35,580
a little bit different of a thought process.

94
00:06:35,580 --> 00:06:42,600
So Ty, if I was thinking five volts DC, what would my brain immediately think of to look

95
00:06:42,600 --> 00:06:47,200
for between the positive terminal and the negative terminal?

96
00:06:47,200 --> 00:06:49,920
Oh, you would think five volts.

97
00:06:49,920 --> 00:06:52,680
Yeah, you would.

98
00:06:52,680 --> 00:06:54,200
That doesn't actually happen.

99
00:06:54,200 --> 00:06:56,700
And here's why.

100
00:06:56,700 --> 00:07:01,760
When we add the reference to ground into that DC circuit, we put that reference to ground,

101
00:07:01,760 --> 00:07:04,980
remember, I said just below its neutral point.

102
00:07:04,980 --> 00:07:11,500
And so we actually have to find ground to be able to check these DC voltages.

103
00:07:11,500 --> 00:07:14,000
And so what did we do with our transformer?

104
00:07:14,000 --> 00:07:15,320
We grounded one side.

105
00:07:15,320 --> 00:07:17,640
Yes, to common.

106
00:07:17,640 --> 00:07:26,920
So on the DC communicating Daikin platform, we simply put our meter on the volts DC.

107
00:07:26,920 --> 00:07:37,880
We use ground or common as our reference point, and we can go from ground to number one, and

108
00:07:37,880 --> 00:07:41,480
we're going to see our DC voltage.

109
00:07:41,480 --> 00:07:45,440
And it's actually going to typically will be around 2.8 volts DC on the gas furnace.

110
00:07:45,440 --> 00:07:48,800
Air handler is a little bit different, but on the gas furnace, we're going to see about

111
00:07:48,800 --> 00:07:56,360
a 2.8 volts DC from common or ground to that positive terminal.

112
00:07:56,360 --> 00:08:02,820
And then if we keep our one terminal on ground and we go to that number two, we actually

113
00:08:02,820 --> 00:08:10,800
read a negative DC voltage because it is below ground.

114
00:08:10,800 --> 00:08:11,800
Kind of makes sense?

115
00:08:11,800 --> 00:08:13,600
It does make sense.

116
00:08:13,600 --> 00:08:18,180
And between the two, we actually have five volts DC.

117
00:08:18,180 --> 00:08:23,240
But because one of them is going above ground 2.8 volts and one of them is going below ground

118
00:08:23,240 --> 00:08:30,360
2.2 volts, it actually calculates out to five volt DC.

119
00:08:30,360 --> 00:08:38,800
So if I was to take my meter, Ty, and I went between number one and number two, and I was

120
00:08:38,800 --> 00:08:45,320
expecting to read five volts DC, but I didn't read five volts DC, what do you think we might

121
00:08:45,320 --> 00:08:47,680
see between number one and number two?

122
00:08:47,680 --> 00:08:50,200
Oh, you got me, Cliff.

123
00:08:50,200 --> 00:08:51,200
I don't know.

124
00:08:51,200 --> 00:08:52,200
I know.

125
00:08:52,200 --> 00:08:53,680
This got me stuck from the beginning.

126
00:08:53,680 --> 00:08:54,880
So think about that.

127
00:08:54,880 --> 00:08:57,680
As we're driving down the road, we're doing a sequence of operation, we're preparing to

128
00:08:57,680 --> 00:09:03,840
go to this Daikin communicating system, and we want to check our communicating voltages.

129
00:09:03,840 --> 00:09:07,780
If we were thinking about it as a five volt DC system, and I was expecting to see five

130
00:09:07,780 --> 00:09:11,460
volts DC and I didn't, I might think that there was a problem.

131
00:09:11,460 --> 00:09:21,700
But because we went above the ground reference 2.8 volts for one point, and we went below

132
00:09:21,700 --> 00:09:28,500
the ground 2.2, a negative 2.2 volts DC, on the other point, when we measure from those

133
00:09:28,500 --> 00:09:32,820
two points, we actually add them together.

134
00:09:32,820 --> 00:09:40,360
A positive 2.8 minus the 2.2, that negative 2.2.

135
00:09:40,360 --> 00:09:47,580
So what we end up with on the number one to number two terminal should be approximately

136
00:09:47,580 --> 00:09:50,120
0.6 volts DC.

137
00:09:50,120 --> 00:09:52,840
Right, that makes sense.

138
00:09:52,840 --> 00:09:53,840
Yeah.

139
00:09:53,840 --> 00:09:56,200
So we have to change our thought process.

140
00:09:56,200 --> 00:10:00,040
AC, we always think about AC as being positive.

141
00:10:00,040 --> 00:10:06,640
Even though it's really, when we look at the sine wave, it's got a positive and negative

142
00:10:06,640 --> 00:10:07,640
reference.

143
00:10:07,640 --> 00:10:09,960
We're typically looking for an RMS voltages in that.

144
00:10:09,960 --> 00:10:16,160
But in DC, we truly can have voltages above the ground reference and voltages below the

145
00:10:16,160 --> 00:10:17,800
ground reference.

146
00:10:17,800 --> 00:10:24,120
So on that DICAN communicating system, when I go between number one and number two, I'm

147
00:10:24,120 --> 00:10:29,600
actually looking for 0.6 volts DC or greater.

148
00:10:29,600 --> 00:10:36,720
And the reason being is that 0.6 volts DC is our bandwidth for our signals to communicate

149
00:10:36,720 --> 00:10:38,120
on.

150
00:10:38,120 --> 00:10:44,840
And if I have less than 0.6 volts DC, that means that my positive and my negative signals

151
00:10:44,840 --> 00:10:48,160
have been affected by something.

152
00:10:48,160 --> 00:10:50,440
I've got a break in the wire.

153
00:10:50,440 --> 00:10:52,800
I've got a bad connection.

154
00:10:52,800 --> 00:10:58,760
I've got a control wire that I reuse that was chewed up by a mouse and got corroded

155
00:10:58,760 --> 00:11:04,040
and worked fine on 24 volts AC but doesn't like 5 volts DC.

156
00:11:04,040 --> 00:11:08,440
It's actually some of the most common things that we see for the communication.

157
00:11:08,440 --> 00:11:13,240
So what we do when we're troubleshooting a DC communicating system on these, particularly

158
00:11:13,240 --> 00:11:16,840
the DICAN, is we disconnect everything.

159
00:11:16,840 --> 00:11:18,480
We start at our indoor unit.

160
00:11:18,480 --> 00:11:23,920
And if it is the gas furnace, we're going to see a 2.8 and a minus 2.2 from ground to

161
00:11:23,920 --> 00:11:25,660
number one, ground to number two.

162
00:11:25,660 --> 00:11:33,040
If it's an air handler, it'll sometimes be less and be like 1.9 and 1.3.

163
00:11:33,040 --> 00:11:36,320
They use more of a 3 volt DC versus that 5 volt.

164
00:11:36,320 --> 00:11:44,880
But the most important part is that we have a 0.6 volt bias or greater between number

165
00:11:44,880 --> 00:11:47,480
one and number two.

166
00:11:47,480 --> 00:11:51,520
If I don't, I've got a problem.

167
00:11:51,520 --> 00:11:54,800
Now Ty, let's think about this.

168
00:11:54,800 --> 00:12:07,320
If I don't have my proper voltages in reference to common, is there any place that I could

169
00:12:07,320 --> 00:12:16,040
possibly look to find a problem with why I don't have a good common reference?

170
00:12:16,040 --> 00:12:19,880
I would start looking at the connections first.

171
00:12:19,880 --> 00:12:22,480
In particularly the connections to ground.

172
00:12:22,480 --> 00:12:23,660
Yes.

173
00:12:23,660 --> 00:12:27,080
So here's one of the things that we see out in the field, especially here in the Midwest,

174
00:12:27,080 --> 00:12:32,400
where we have old wiring and a lot of furnaces were only wired with a hot and a neutral and

175
00:12:32,400 --> 00:12:33,760
didn't have a proper ground.

176
00:12:33,760 --> 00:12:36,840
I mean, we'd see that and go, oh my gosh, does that really happen?

177
00:12:36,840 --> 00:12:38,620
Yes, it absolutely happens.

178
00:12:38,620 --> 00:12:45,740
And so what we have is we have the potential for a bad ground to that indoor unit to throw

179
00:12:45,740 --> 00:12:47,760
off those DC voltages.

180
00:12:47,760 --> 00:12:52,840
And so unfortunately, a lot of technicians, if they were learning how to check the voltages

181
00:12:52,840 --> 00:12:58,360
and they measured and they found that they had no voltage or very, very low voltage,

182
00:12:58,360 --> 00:13:02,120
they would immediately go to the indoor board to replace it.

183
00:13:02,120 --> 00:13:07,680
In actuality, we need to verify the ground to the indoor unit.

184
00:13:07,680 --> 00:13:12,960
And Ty, what are some good ways we can check ground coming into the power supply of our

185
00:13:12,960 --> 00:13:14,760
indoor unit?

186
00:13:14,760 --> 00:13:17,120
The ground lug, the ground terminal?

187
00:13:17,120 --> 00:13:18,240
Absolutely.

188
00:13:18,240 --> 00:13:25,180
So what we end up finding a lot of times on that ground is if it has a bad connection,

189
00:13:25,180 --> 00:13:27,200
we can lose that potential.

190
00:13:27,200 --> 00:13:33,200
So what I always like to do is to be able to check the voltages from ground to our hot,

191
00:13:33,200 --> 00:13:37,200
make sure that we have, if it's a 120 volt system, we've got 120 volt from ground to

192
00:13:37,200 --> 00:13:41,140
hot and we have the exact same voltage from neutral to hot.

193
00:13:41,140 --> 00:13:45,820
And if there's any difference in those voltages, we know that we've had some kind of a bad

194
00:13:45,820 --> 00:13:51,600
connection on that ground lug or a poor connection of ground somewhere or no ground.

195
00:13:51,600 --> 00:13:56,640
And so if there's a difference in those voltages from ground to hot and neutral to hot, we

196
00:13:56,640 --> 00:14:01,200
know that we have either on that neutral or that ground, we have some kind of a failure,

197
00:14:01,200 --> 00:14:03,280
some kind of an interruption.

198
00:14:03,280 --> 00:14:09,060
So if we verify that we have good ground, we've started our indoor board and we have

199
00:14:09,060 --> 00:14:15,800
0.6 volts or greater, we know that we have started with a good DC voltage.

200
00:14:15,800 --> 00:14:19,520
And now we would connect the indoor communicating thermostat.

201
00:14:19,520 --> 00:14:21,280
So we connect those four wires.

202
00:14:21,280 --> 00:14:29,840
And so from common to R, I got to put my meter on, how about volts AC?

203
00:14:29,840 --> 00:14:32,240
Make sure that I got my 24 volts AC.

204
00:14:32,240 --> 00:14:40,160
But then from common to one and common to two, that's where I would have my DC voltages.

205
00:14:40,160 --> 00:14:45,040
And so I connect the indoor thermostat and I check my voltages between number one and

206
00:14:45,040 --> 00:14:47,800
number two at the thermostat.

207
00:14:47,800 --> 00:14:51,960
And it should be the same as what I had started with my indoor unit because that thermostat

208
00:14:51,960 --> 00:14:53,480
doesn't have much of a load on it.

209
00:14:53,480 --> 00:14:55,880
It's just communicating.

210
00:14:55,880 --> 00:15:06,960
Now if I connect my outdoor unit and my voltages, my DC voltages get janky, now I've actually

211
00:15:06,960 --> 00:15:10,680
determined a place to look for my problems.

212
00:15:10,680 --> 00:15:17,600
And here's where the most common failure on a communicating system on the outdoor unit

213
00:15:17,600 --> 00:15:19,020
comes from.

214
00:15:19,020 --> 00:15:24,880
So Ty, as a technician, and we were working on a AC powered outdoor unit.

215
00:15:24,880 --> 00:15:30,480
So whether a single stage, two stage, whatever it was, if it was just a plain Jane, I got

216
00:15:30,480 --> 00:15:36,680
a compressor, a contactor, and a motor and a capacitor.

217
00:15:36,680 --> 00:15:39,080
Did it really care about ground?

218
00:15:39,080 --> 00:15:41,320
Nope, not at all.

219
00:15:41,320 --> 00:15:45,720
Because it would still run on common and hot.

220
00:15:45,720 --> 00:15:53,760
It only used ground as a reference point if it had a failure and it had current being

221
00:15:53,760 --> 00:15:57,120
able to make its way back to the panel through the ground circuit.

222
00:15:57,120 --> 00:16:02,560
So with our traditional legacy systems, ground was not really important for the outdoor unit

223
00:16:02,560 --> 00:16:04,280
except for safety.

224
00:16:04,280 --> 00:16:05,800
Okay?

225
00:16:05,800 --> 00:16:08,760
So let's think about this.

226
00:16:08,760 --> 00:16:14,680
Because my communicating system relies on the reference to ground and because my new

227
00:16:14,680 --> 00:16:25,360
unit has power from its own power supply outside, where does it get common or the ground reference

228
00:16:25,360 --> 00:16:28,920
for number one and number two?

229
00:16:28,920 --> 00:16:35,640
This is where I sit in class and go, do, do, do, do, do, do, do.

230
00:16:35,640 --> 00:16:43,560
Where my mind is running is if the grounding rod outside is corroded, which often happens,

231
00:16:43,560 --> 00:16:47,080
then that could also lead to an issue with your communication system because it's not

232
00:16:47,080 --> 00:16:49,240
having a reference to ground.

233
00:16:49,240 --> 00:16:50,720
Bingo.

234
00:16:50,720 --> 00:16:56,800
The most common misdiagnosed portion of a failed communicating system when it's referenced

235
00:16:56,800 --> 00:17:02,360
to the outdoor unit is the ground connection back to the electrical panel or through the

236
00:17:02,360 --> 00:17:05,120
grounded of the circuit.

237
00:17:05,120 --> 00:17:12,440
Because when it was engineered, they assumed that all electrical systems were properly

238
00:17:12,440 --> 00:17:15,760
grounded, including the outdoor unit.

239
00:17:15,760 --> 00:17:21,520
And so when that 24 volt common and 24 volt hot was removed from the circuit going to

240
00:17:21,520 --> 00:17:27,960
the outdoor unit and it only had number one and number two, those DC voltages that were

241
00:17:27,960 --> 00:17:36,400
referencing or signaling to ground, the assumption was that they would get that path from ground

242
00:17:36,400 --> 00:17:38,440
of the outdoor unit.

243
00:17:38,440 --> 00:17:45,360
And so what often gets overlooked is the ground from the outdoor unit to the disconnect, to

244
00:17:45,360 --> 00:17:50,780
the ground rod, or to the back to the ground of the indoor panel, the electrical panel.

245
00:17:50,780 --> 00:17:55,400
And so how we find that is we do that same DC voltage check.

246
00:17:55,400 --> 00:18:01,400
So we check from common to number one and then common to number two to look for that

247
00:18:01,400 --> 00:18:05,000
0.6 volt DC difference at the indoor unit and at the thermostat.

248
00:18:05,000 --> 00:18:13,160
When we go to the outdoor unit, since we don't have common, we now use ground because it

249
00:18:13,160 --> 00:18:14,160
is our common.

250
00:18:14,160 --> 00:18:19,440
And if we don't have those same signals and it's an immediate indicator that we have a

251
00:18:19,440 --> 00:18:27,040
poor ground between the outdoor unit and the disconnect and the electrical panel.

252
00:18:27,040 --> 00:18:31,200
And a lot of technicians don't realize what that is.

253
00:18:31,200 --> 00:18:36,160
They assume that those two wires that are going to the outdoor unit, all of the communication

254
00:18:36,160 --> 00:18:38,800
is happening on those two wires alone.

255
00:18:38,800 --> 00:18:45,120
And that is somewhat true, but the circuit relies on ground for the reference point for

256
00:18:45,120 --> 00:18:46,720
those DC voltages.

257
00:18:46,720 --> 00:18:52,280
And if we have a bad ground, if we have a corroded lug, if we have a ground wire that

258
00:18:52,280 --> 00:18:58,720
is rotten, is not making good connection, if we have what I've also seen in some of

259
00:18:58,720 --> 00:19:04,240
the older disconnects, they used aluminum lug screws for the ground wire.

260
00:19:04,240 --> 00:19:09,280
And those aluminum lug screws when connected to copper oxidize and corrode really bad and

261
00:19:09,280 --> 00:19:12,080
they actually lose their conductivity.

262
00:19:12,080 --> 00:19:18,280
So I've had troubleshooting calls that were non-communicating outdoor units that the fix

263
00:19:18,280 --> 00:19:24,440
was as simple as loosening the screws, cleaning off the corrosion, putting some dielectric

264
00:19:24,440 --> 00:19:30,880
grease and cranking them back down to restore our communication to ground and our communicating

265
00:19:30,880 --> 00:19:32,960
systems start talking.

266
00:19:32,960 --> 00:19:33,960
That's interesting.

267
00:19:33,960 --> 00:19:35,420
Isn't that crazy?

268
00:19:35,420 --> 00:19:41,640
So when we start thinking about DC communicating systems, our sequence of operation is we begin

269
00:19:41,640 --> 00:19:43,500
at the indoor unit.

270
00:19:43,500 --> 00:19:50,680
We verify our voltages from ground or common to number one and to number two.

271
00:19:50,680 --> 00:19:55,240
We check the DC voltages between number one and number two to make sure we have 0.6 volts

272
00:19:55,240 --> 00:19:58,360
DC bias or greater.

273
00:19:58,360 --> 00:20:03,320
We check our indoor unit, we add the thermostat to the indoor unit, we check our thermostat.

274
00:20:03,320 --> 00:20:08,880
And then when those are the same, we add the outdoor unit and make sure that nothing changed.

275
00:20:08,880 --> 00:20:14,920
In the instance that we have an extremely long control wire from the indoor unit to

276
00:20:14,920 --> 00:20:19,760
the outdoor unit or we have poor conductors, it's actually going to show itself.

277
00:20:19,760 --> 00:20:24,320
And in some cases, we have to increase that bias voltage.

278
00:20:24,320 --> 00:20:30,140
And on those DICON units, they actually have a switch on the outdoor unit that boost that

279
00:20:30,140 --> 00:20:31,520
bias voltage.

280
00:20:31,520 --> 00:20:34,420
It opens up that bandwidth a little bit.

281
00:20:34,420 --> 00:20:40,760
And so on some systems, when our bias is lower than 0.6 volts DC, we have to engage that

282
00:20:40,760 --> 00:20:45,760
to be able to make sure that we have above 0.6 volts DC.

283
00:20:45,760 --> 00:20:51,720
Because that 0.6 volts DC might be good right now, but because it's in reference to ground,

284
00:20:51,720 --> 00:20:56,840
it could change the next time that it rains or the next time that it gets really dry and

285
00:20:56,840 --> 00:20:59,360
arid outside and affects ground.

286
00:20:59,360 --> 00:21:02,760
And that 0.6 volt DC bias can drop.

287
00:21:02,760 --> 00:21:12,200
So moral of the story, on a DICON in particularly, 5 volt DC communicating system, we must check

288
00:21:12,200 --> 00:21:18,160
from common to one, common to two, and the difference between one and two shall be 0.6

289
00:21:18,160 --> 00:21:21,840
volts DC or greater, or you're coming back.

290
00:21:21,840 --> 00:21:22,840
That's interesting.

291
00:21:22,840 --> 00:21:24,800
I did not know that.

292
00:21:24,800 --> 00:21:26,760
I love that.

293
00:21:26,760 --> 00:21:30,760
All right, Ty, thanks for joining us and we appreciate having a conversation on DC voltages

294
00:21:30,760 --> 00:21:33,520
and we'll catch you next time on Did You Know?

295
00:21:33,520 --> 00:21:42,540
The Esco HVAC Podcast.

