1
00:00:00,000 --> 00:00:05,900
Welcome back to Teaching the Unteachables where we dive into teaching and learning

2
00:00:05,900 --> 00:00:12,000
methodologies for professionals like you. This episode brought to you by Joey

3
00:00:12,000 --> 00:00:21,460
Henderson otherwise known as JoeJoe the HVAC man. Learn more at JoeJoeHVAC.com

4
00:00:21,460 --> 00:00:30,460
Well hello everyone thank you for joining Did You Know the ESCO HVAC podcast. So

5
00:00:30,460 --> 00:00:35,120
today we're hanging out with Joey Henderson otherwise known as JoeJoe the HVAC man.

6
00:00:35,120 --> 00:00:40,680
How are you my friend? I'm doing fantastic thank you. Hey Joey what happens if the

7
00:00:40,680 --> 00:00:47,600
next refrigerant generation we see is milk? Well first I want to be nice and

8
00:00:47,600 --> 00:00:52,920
cold whenever I get some out of it. Other than that we'll use it just like

9
00:00:52,920 --> 00:00:57,640
we do any other refrigerant. Right just be a refrigerant. It's just a

10
00:00:57,640 --> 00:01:01,800
refrigerant that's all. We always get caught up on you know oh man this new

11
00:01:01,800 --> 00:01:05,280
refrigerant got high pressure oh man is this refrigerant gonna be flammable oh

12
00:01:05,280 --> 00:01:11,200
man what does it really come down to? You know that's a great question and

13
00:01:11,200 --> 00:01:14,800
it's always been the same we got a certain saturation temperature in the

14
00:01:14,800 --> 00:01:17,740
condenser and a certain saturation in the evaporator and that's all we're

15
00:01:17,740 --> 00:01:21,760
worried about no matter what flavor of ice cream is inside that unit. Ain't that

16
00:01:21,760 --> 00:01:26,240
a great way to think about it and we forget about that. Yeah we get caught up

17
00:01:26,240 --> 00:01:30,380
on what is going to be different and we don't really think about well what's

18
00:01:30,380 --> 00:01:35,320
gonna be the same. Right right right there's like any other thing there are

19
00:01:35,320 --> 00:01:39,520
variables and you know but we got to focus on the constant and there are

20
00:01:39,520 --> 00:01:47,280
constants and to keep it simple because I'm a simple man you know is the

21
00:01:47,280 --> 00:01:53,480
saturated condenser temperature is always these days you know we used to be 30

22
00:01:53,480 --> 00:01:57,280
degrees above ambient and let me just explain tell you this real quick when I

23
00:01:57,280 --> 00:02:00,880
was in the field and I heard that 30 over ambient you know we're both back

24
00:02:00,880 --> 00:02:05,960
from the the eight sear days and you know 10 sear was wow and 12 sear was

25
00:02:05,960 --> 00:02:10,560
unheard of all right you know but you know those condensers you know were

26
00:02:10,560 --> 00:02:16,400
small and tiny and we got we were told 30 degrees above ambient well in my my

27
00:02:16,400 --> 00:02:19,680
mind I got turned around because I was so used to reading air coming in and

28
00:02:19,680 --> 00:02:23,240
air going out across the evaporator well I thought I was supposed to measure the

29
00:02:23,240 --> 00:02:26,120
air coming into the condenser and the air coming out the top of the condenser

30
00:02:26,120 --> 00:02:30,120
like a split yeah and it never worked so I threw it in the garbage and never went

31
00:02:30,120 --> 00:02:35,600
back when I finally got educated and found out oh it's outside air temperature

32
00:02:35,600 --> 00:02:40,440
versus the saturation temperature in the condenser well it came simpler these

33
00:02:40,440 --> 00:02:46,480
days our average unit out there your 14 to 16 sear is gonna run between 15 and

34
00:02:46,480 --> 00:02:52,120
20 degrees above ambient so it's very simple you know if it's 90 degrees

35
00:02:52,120 --> 00:02:56,720
outside you add 20 you're looking for 110 degree condensing temperature and

36
00:02:56,720 --> 00:03:00,320
then you convert that to pressure and it don't matter what refrigerates in there

37
00:03:00,320 --> 00:03:04,280
now you know what pressure you ought to be looking at but first just make sure

38
00:03:04,280 --> 00:03:07,760
you got the right saturation and it works every time yeah and so it's as

39
00:03:07,760 --> 00:03:12,760
simple as all right we always preach airflow overcharge right so if we have

40
00:03:12,760 --> 00:03:16,480
verified that the outdoor unit is getting proper airflow and the indoor

41
00:03:16,480 --> 00:03:20,480
unit is getting proper airflow now we can simply look at it from a temperature

42
00:03:20,480 --> 00:03:25,680
perspective that's right that's right and you're right yeah this does work all

43
00:03:25,680 --> 00:03:30,800
the fact that holes are clean filters are clean airflow is correct exactly so

44
00:03:30,800 --> 00:03:34,400
if we think about that and we look at refrigerant because we're going through

45
00:03:34,400 --> 00:03:37,880
a refrigerant change and there's gonna be a lot of people very concerned with

46
00:03:37,880 --> 00:03:40,760
this refrigerant change going oh man I keep hearing it's gonna be mildly

47
00:03:40,760 --> 00:03:44,480
flammable we get into a threes are gonna be highly flammable all my pressures

48
00:03:44,480 --> 00:03:48,040
what my gauges aren't gonna look the same I won't know what to do and it

49
00:03:48,040 --> 00:03:51,920
always comes back to yeah you do you just you're over complicating things

50
00:03:51,920 --> 00:03:56,840
that's right that's right an evaporator temperature on an air conditioning system

51
00:03:56,840 --> 00:04:02,760
has never really changed when we went through these refrigerant changes it

52
00:04:02,760 --> 00:04:08,880
never has I you know so you and I got in the field similar timeframe you know and

53
00:04:08,880 --> 00:04:13,480
so when I jumped in out of the Navy and stepped into the residential commercial

54
00:04:13,480 --> 00:04:18,120
world all of a sudden our 12 was being shot down and our 22 was being shot

55
00:04:18,120 --> 00:04:20,760
down and we had to go to new refrigerants and it was like oh my gosh

56
00:04:20,760 --> 00:04:25,840
you know well when I got the job with carrier and we were really really pushing

57
00:04:25,840 --> 00:04:30,600
for 10a training I had guys think the unit was gonna blow up they thought it

58
00:04:30,600 --> 00:04:35,800
was crazy you know but it's this every unit is designed for whatever pressure

59
00:04:35,800 --> 00:04:40,520
they want to put in them yeah but the temperature never changed the the

60
00:04:40,520 --> 00:04:46,000
saturation temperature is always centered around the application so if

61
00:04:46,000 --> 00:04:50,240
it's air conditioning the evaporator coil has adjusted a little bit we were

62
00:04:50,240 --> 00:04:54,640
running closer to a 35 degree evaporator coil back in the old days and then we've

63
00:04:54,640 --> 00:05:00,320
kind of raised it and on average a run in 40 42 I've seen some as high as 45 but

64
00:05:00,320 --> 00:05:04,120
on average again we're just keeping it simple you know on average about a 40

65
00:05:04,120 --> 00:05:08,440
degree evaporator suction we look at about a 35 degree split between return

66
00:05:08,440 --> 00:05:12,640
air and saturation temperature in the coil that way we get the laying in the

67
00:05:12,640 --> 00:05:16,920
sensible removal with the proper airflow right right and then you get to these

68
00:05:16,920 --> 00:05:20,040
condensers and now since they're making them they you know they used to be three

69
00:05:20,040 --> 00:05:26,160
foot tall now they're you know 15 foot tall you know you only got three options

70
00:05:26,160 --> 00:05:28,800
when it comes to a condenser design to get it high efficient you're either

71
00:05:28,800 --> 00:05:32,560
gonna expand the diameter of it so it won't fit in the backyard or through the

72
00:05:32,560 --> 00:05:36,600
gate to get in there right or they're gonna make it a tower that looks like a

73
00:05:36,600 --> 00:05:40,800
cooling tower outside the back of your house or they'll double it so you'll

74
00:05:40,800 --> 00:05:46,320
have the dual the evaporator overlay and just a side note guys don't forget to

75
00:05:46,320 --> 00:05:51,800
split that thing open and wash it in between inside I've dropped I've dropped

76
00:05:51,800 --> 00:05:55,880
a unit a hundred psi just by cracking it open and it doesn't look that bad but I

77
00:05:55,880 --> 00:05:59,880
promise you it's like a film of plastic in between those two coils the other

78
00:05:59,880 --> 00:06:03,760
little side note but you know get all that clean and then you know the

79
00:06:03,760 --> 00:06:06,800
condensate you know what head pressure should I be looking for

80
00:06:06,800 --> 00:06:09,800
that's always remember what's my pressures be right what's my pressures

81
00:06:09,800 --> 00:06:14,680
you know yeah doesn't matter at the moment find out what your saturation

82
00:06:14,680 --> 00:06:18,200
should be then you can convert that to the pressure whatever refrigerant

83
00:06:18,200 --> 00:06:23,240
including milk exactly because we think about you and I got a patent coming up

84
00:06:23,240 --> 00:06:30,720
right on milk refrigerant you know what that would be a blended refrigerant if we

85
00:06:30,720 --> 00:06:39,280
take our 718 which is h2o and we blend it with lactose which I don't even know

86
00:06:39,280 --> 00:06:45,480
we could probably patent the the PT chart for lactose and then we blend the

87
00:06:45,480 --> 00:06:51,440
two of those and we got milk and we're gonna call that oh that's gonna be

88
00:06:51,440 --> 00:06:57,840
that's not an MO refrigerant that's an MOO refrigerator

89
00:06:57,840 --> 00:07:10,080
so if we think about that right if we had one chemical in it alone that's a

90
00:07:10,080 --> 00:07:14,600
single constituent refrigerant if I blend a couple of them well now I've got

91
00:07:14,600 --> 00:07:18,640
two refrigerants that are taking up the same space and they might boil off a

92
00:07:18,640 --> 00:07:24,200
little bit different right and we are gonna see that going into our new

93
00:07:24,200 --> 00:07:27,880
generations of refrigerants for air conditioning if we think about like r22

94
00:07:27,880 --> 00:07:36,400
r22 was a single constituent refrigerant it had r22 right when we went to r410A

95
00:07:36,400 --> 00:07:40,280
we were actually working with the blended refrigerant but we we never

96
00:07:40,280 --> 00:07:51,640
talked about it enough r410A is a blend a 50-50 blend of r32 and r125 right we

97
00:07:51,640 --> 00:07:57,160
weren't ready for the mildly flammable refrigerant r32 so we threw some flame

98
00:07:57,160 --> 00:08:01,720
deterrent called 125 in there and we end up with 410A that's right so the reason

99
00:08:01,720 --> 00:08:04,480
we had to flip the jug upside down when we were charging it because we had to

100
00:08:04,480 --> 00:08:08,520
charge it with the liquid because it had that glide that little bitty potential

101
00:08:08,520 --> 00:08:14,480
for boiling off it very very small now when we move into r32 well we are moving

102
00:08:14,480 --> 00:08:19,760
into r32 and 454 they're already hitting the streets r32 is a single

103
00:08:19,760 --> 00:08:24,760
constituent refrigerant remember it was half of our 410A so on my PT chart boom

104
00:08:24,760 --> 00:08:29,520
whatever my pressure is my temperature should be this right now with 454B

105
00:08:29,520 --> 00:08:33,480
we're actually gonna have some glide and so I think it's great to talk about

106
00:08:33,480 --> 00:08:37,920
blended refrigerants and just really to understand that what that means is in a

107
00:08:37,920 --> 00:08:43,240
little window we could have one refrigerant if we're if we're raising the

108
00:08:43,240 --> 00:08:47,000
pressure we can have one refrigerant boil off at a temperature and the other

109
00:08:47,000 --> 00:08:52,240
one be catching up but not quite done right so there's a little window in

110
00:08:52,240 --> 00:08:57,400
there between when it's totally a vapor and below when it's totally a liquid now

111
00:08:57,400 --> 00:09:02,840
is it gonna matter with our digital gauges not much it's got to calculate

112
00:09:02,840 --> 00:09:07,360
that difference yeah they're gonna calculate it for us yeah you know I and

113
00:09:07,360 --> 00:09:12,280
I like the way you put it because dew and bubble just just every time I heard

114
00:09:12,280 --> 00:09:16,480
somebody explain it I you know at some point my brain checked out because it

115
00:09:16,480 --> 00:09:19,720
just got complicated right now so last thing I hate is something complicated

116
00:09:19,720 --> 00:09:24,440
again I'm a simple man so I want to keep it simple and like you said on the dew

117
00:09:24,440 --> 00:09:30,840
and the bubble you know you got you know at the dew when you we got a dew point

118
00:09:30,840 --> 00:09:38,000
temperature you know we're looking at a hundred degrees saturation and at 315

119
00:09:38,000 --> 00:09:42,760
psig we're right at the cusp and anything above that we're gonna be a

120
00:09:42,760 --> 00:09:48,880
total gas that would be superheated gas yep right and then on the bubble which

121
00:09:48,880 --> 00:09:52,160
would be the lower end of the pressure range go through that little window of

122
00:09:52,160 --> 00:09:56,000
glide right we're gliding we're basically we're dropping down kind of

123
00:09:56,000 --> 00:09:59,440
think of the movie the abyss we're dropping down that's right so finally

124
00:09:59,440 --> 00:10:05,040
when we hit the bottom down where the mega shark lives you know we've now hit

125
00:10:05,040 --> 00:10:10,480
true liquid right but back in the day you and I we all carried in our little

126
00:10:10,480 --> 00:10:14,160
pocket these little PT charts you know and then they made them out with these

127
00:10:14,160 --> 00:10:19,880
do a bubble and we all lost our minds you know but the now with the digital

128
00:10:19,880 --> 00:10:24,520
gauges that have it all built in for us they're not gonna I haven't seen yet

129
00:10:24,520 --> 00:10:27,240
where they show bubble and do they're pretty much gonna take an average

130
00:10:27,240 --> 00:10:30,840
between that window and that's exactly what they're gonna do and you know you

131
00:10:30,840 --> 00:10:34,600
can you can figure out your subcooling your superheat the same way you always

132
00:10:34,600 --> 00:10:40,560
have of course these days are doing it for you you know so you got to trust it

133
00:10:40,560 --> 00:10:43,160
the only you're gonna you know the only left is you know whether or not your

134
00:10:43,160 --> 00:10:48,720
sensors are accurate or not so but I don't really like to get too caught up

135
00:10:48,720 --> 00:10:53,120
in the weeds with doing bubble it is what it is it's a short window so I'm

136
00:10:53,120 --> 00:10:57,120
a little it's definitely bigger compared to like you said for 10 a by all means

137
00:10:57,120 --> 00:11:02,640
but in the end we're still gonna go for an average target condensing temperature

138
00:11:02,640 --> 00:11:09,560
and a target evaporator that's it and then we can troubleshoot from there is

139
00:11:09,560 --> 00:11:12,240
my head pressure running too high well darn I don't know these new

140
00:11:12,240 --> 00:11:15,560
refrigerants you know maybe it's 600 I don't know you know well no it's not you

141
00:11:15,560 --> 00:11:25,760
know 454 B are 32 are close to 410 a you know not perfect but it's not being that

142
00:11:25,760 --> 00:11:29,120
crazy when you and I came through and they went from R12 a lot I wasn't

143
00:11:29,120 --> 00:11:34,480
around we went from R12 to R22 in a sees all right I was when we went from R12 to

144
00:11:34,480 --> 00:11:39,240
134 a in refrigeration refrigeration but we went from 22 to 410 a that was a

145
00:11:39,240 --> 00:11:45,320
substantial increase absolutely you know and we also changed oils we had a major

146
00:11:45,320 --> 00:11:51,120
transformation back in the 90s early 90s here we've already got POE oil we've all

147
00:11:51,120 --> 00:11:58,720
got that stuck in our heads and now really the 454 B and R32 is just not

148
00:11:58,720 --> 00:12:04,760
that big of a change on the operation we're gonna see 32 go up a few yeah

149
00:12:04,760 --> 00:12:10,160
we're gonna see 454 go down a few that's right and a few is a is a is the right

150
00:12:10,160 --> 00:12:14,520
way to say it yeah it's literally just a few I mean if you're not used to reading

151
00:12:14,520 --> 00:12:17,040
temperatures and pressures anyhow you're gonna put them gauges on it's

152
00:12:17,040 --> 00:12:20,960
gonna look almost identical to what you have in the past it really is and you

153
00:12:20,960 --> 00:12:24,400
know we you and I we got this little chart up here in front of us and you

154
00:12:24,400 --> 00:12:31,320
look at a hundred degree condensing temperature for 410 a and you and you've

155
00:12:31,320 --> 00:12:35,880
even got that little bit of a glide in there but let's just say it's 333 you

156
00:12:35,880 --> 00:12:39,480
know and you know that was so average you know when I started doing training

157
00:12:39,480 --> 00:12:43,000
for 410 a with carrier they were guesstimating because we hadn't had a

158
00:12:43,000 --> 00:12:46,720
unit out there yet I was certified for today two years before one even hit the

159
00:12:46,720 --> 00:12:50,800
streets right and they were telling us 400 head pressure 400 head pressure I

160
00:12:50,800 --> 00:12:56,200
never saw a foreigner had pressure in my life on 410 a it was 335 and 340 and

161
00:12:56,200 --> 00:13:01,800
guess what that is 100 to 105 condensing and that is designed no matter what

162
00:13:01,800 --> 00:13:08,760
refrigerant it is and then you go over here to 454 B and sure enough I mean you

163
00:13:08,760 --> 00:13:14,140
look at the average between 454 B and it's between 305 and 315 so we're kind

164
00:13:14,140 --> 00:13:19,180
of hitting in the middle there a little bit lower than 410 a and you know r32 is

165
00:13:19,180 --> 00:13:25,080
gonna be almost the same it's like 340 so a little higher no freaking out it's

166
00:13:25,080 --> 00:13:29,560
it's okay you know absolutely you know just keep doing what you're doing keep

167
00:13:29,560 --> 00:13:35,160
it simple you know and you'll be alright but now you know that if it's 95 outside

168
00:13:35,160 --> 00:13:41,320
let's say it's 105 outside you know add 20 to that and that's where your

169
00:13:41,320 --> 00:13:46,200
saturation temperature ought to be and then convert that to whatever refrigerant

170
00:13:46,200 --> 00:13:50,160
pressure you're working on absolutely if I was working with something like co2

171
00:13:50,160 --> 00:13:53,700
people go I don't know what it would be like to work on co2 what kind of head

172
00:13:53,700 --> 00:13:58,880
pressure am I gonna have well hundred degrees 1363 it's a lot of pressure

173
00:13:58,880 --> 00:14:03,140
that's the kind of pressures we need to educate on when we're talking about high

174
00:14:03,140 --> 00:14:08,180
pressures 22 to 410 is not high pressure change that's all right we'll make the

175
00:14:08,180 --> 00:14:13,280
cold out of titanium yeah 410 to co2 now we're talking what about water right

176
00:14:13,280 --> 00:14:22,560
we're gonna make our new you know new we call it move to move to move to 22 we're

177
00:14:22,560 --> 00:14:27,520
actually gonna be in vacuum at a hundred degrees we're gonna be at 28 inches

178
00:14:27,520 --> 00:14:32,280
right so water is absolutely a refrigerant can I have the exact same

179
00:14:32,280 --> 00:14:37,520
evaporator temperature and condensing temperature and just use water

180
00:14:37,520 --> 00:14:45,640
absolutely yep so I could run an air conditioning system on water or milk

181
00:14:45,640 --> 00:14:50,480
it's just gonna be in vacuum on both sides that's right that's right everybody

182
00:14:50,480 --> 00:14:54,560
gotta remember this podcast because down the way when you guys are buying milk

183
00:14:54,560 --> 00:15:03,520
out of the grocery store for your fridge remember the move 22 guys I mean you

184
00:15:03,520 --> 00:15:09,400
know to just assure our audience it's nothing to worry about it really is you

185
00:15:09,400 --> 00:15:12,280
know these new refrigerants but you know as far as how they're gonna operate in

186
00:15:12,280 --> 00:15:17,040
the system you know yeah we're gonna have some extra sensors on there for

187
00:15:17,040 --> 00:15:21,240
leaks and you know the refrigerant leak the refrigerant sensors out there but

188
00:15:21,240 --> 00:15:27,080
they're slightly flammable they broke the barrier barely barely you know barely

189
00:15:27,080 --> 00:15:31,840
I mean you know Ty just did a great little video put a match right up to it

190
00:15:31,840 --> 00:15:36,840
nothing happened you've done the videos to show it you know and you know it not

191
00:15:36,840 --> 00:15:41,840
gonna now we're not talking about propane no not talking about 290 or 600

192
00:15:41,840 --> 00:15:49,280
we're just talking about 454 B and r32 and no worries no absolutely for just

193
00:15:49,280 --> 00:15:53,600
the sake of conversation because let's think about this like going forward we

194
00:15:53,600 --> 00:15:57,880
are going to have new refrigerants periodically oh yeah it's gonna come

195
00:15:57,880 --> 00:16:02,160
again yeah absolutely you know so many technicians get into the mindset of I'm

196
00:16:02,160 --> 00:16:06,200
learning this refrigerant and it's gonna be here my whole career no this is this

197
00:16:06,200 --> 00:16:10,720
is our this is Joey and I's third refrigerant change right it's up it's

198
00:16:10,720 --> 00:16:15,120
almost a fourth when we look at where we're yeah if we add commercial in there

199
00:16:15,120 --> 00:16:20,160
we're talking about a fourth generation of changes so as we move into the next

200
00:16:20,160 --> 00:16:26,480
generation of changes we are going to go to something else sometime in the next

201
00:16:26,480 --> 00:16:35,440
12 years because remember the HFC phase down will be done by 2036 we will be

202
00:16:35,440 --> 00:16:43,640
down to an 85% reduction of all HFCs including r32 and 454 B so right so we

203
00:16:43,640 --> 00:16:48,160
got a shelf life of these new quote refrigerants we got a shelf life of

204
00:16:48,160 --> 00:16:52,040
about 12 years if they make it that long and we will be moving into another

205
00:16:52,040 --> 00:16:58,240
generation of refrigerants it might be milk we might my golly we may come up

206
00:16:58,240 --> 00:17:05,240
with that million dollar retirement that's right someone might actually work

207
00:17:05,240 --> 00:17:10,760
with mood 22 one day the only thing that's constant is change constant you

208
00:17:10,760 --> 00:17:13,880
can't stop it no there's gonna be a reason you're right I mean we've already

209
00:17:13,880 --> 00:17:19,080
got the phase-out going we inevitably we're gonna have another refrigerant to

210
00:17:19,080 --> 00:17:24,800
even replace these two absolutely that's a given but back to our point it's all

211
00:17:24,800 --> 00:17:29,160
based on design saturation temperatures will not change or air-conditioned right

212
00:17:29,160 --> 00:17:34,180
let's just assume what if we did have propane for air conditioning and and we

213
00:17:34,180 --> 00:17:38,080
took it and we put it outside say we have like an air to water you're looking

214
00:17:38,080 --> 00:17:42,700
at sitting outside we get rid of the line sets that have refrigerant in them

215
00:17:42,700 --> 00:17:47,080
and we have line sets that have water mixed with brine right okay that's right

216
00:17:47,080 --> 00:17:50,920
that's what we're gonna end up with if anyone doesn't know if when we get if we

217
00:17:50,920 --> 00:17:54,760
go to propane we are actually not gonna have refrigerant indoors it's all gonna

218
00:17:54,760 --> 00:17:57,920
be outside but we go get our ages what we're gonna be looking for we're gonna

219
00:17:57,920 --> 00:18:00,800
have a self-contained unit outside it's gonna have an evaporator and a condenser

220
00:18:00,800 --> 00:18:04,000
and because it's air conditioning it's probably gonna have a 40 degree design

221
00:18:04,000 --> 00:18:06,880
evaporator it's gonna have about a hundred degree design on condenser and

222
00:18:06,880 --> 00:18:11,440
if we look at a PT chart now we're gonna go okay well Joe you're just telling me

223
00:18:11,440 --> 00:18:15,840
that I have that design split right and so I look at my approach and I go okay

224
00:18:15,840 --> 00:18:22,040
if I've got a hundred degree condensing temperature and I walk over and I go

225
00:18:22,040 --> 00:18:29,480
well if I was 340 degrees on r32 and now I'm just gonna go ahead and use r290

226
00:18:29,480 --> 00:18:34,160
man I'm gonna drop all the way back down again to 190 yeah I'm gonna be in

227
00:18:34,160 --> 00:18:40,120
between 12 and 22 that's right but temperature wise I could have a

228
00:18:40,120 --> 00:18:44,200
completely new generation of product that's right but I'm still probably

229
00:18:44,200 --> 00:18:47,680
going to design my evaporator and my condensing temperatures about the same

230
00:18:47,680 --> 00:18:51,320
as what we're doing right now that's right because in the end remember we're

231
00:18:51,320 --> 00:18:55,760
either raising the pressure raising the temperature of the refrigerant so that

232
00:18:55,760 --> 00:19:01,440
we can reject the heat with hot air outside yeah right or we're gonna lower

233
00:19:01,440 --> 00:19:05,200
the refrigerant temperature enough to absorb the heat on the inside and that

234
00:19:05,200 --> 00:19:11,880
is all strictly based off of the indoor return air temperature that we're trying

235
00:19:11,880 --> 00:19:16,560
to achieve you know and the latent and sensible removal and again this is all

236
00:19:16,560 --> 00:19:20,680
back to proper airflow and proper clean cold right you know so all that comes

237
00:19:20,680 --> 00:19:23,880
into play you know but you know like you're saying you know we might as well

238
00:19:23,880 --> 00:19:28,040
start looking at you know the more and more we move to trying to get away from

239
00:19:28,040 --> 00:19:31,080
any of these refrigerants and have something like 290 where you can just

240
00:19:31,080 --> 00:19:36,280
let it go you know get out of the way they're gonna be probably circulating

241
00:19:36,280 --> 00:19:39,600
you know like a little chill water system you know just like hydronic

242
00:19:39,600 --> 00:19:43,080
heating we'll have you know chill water through the house and have a little

243
00:19:43,080 --> 00:19:47,720
package unit sitting outside with a small amount of propane in it yeah and

244
00:19:47,720 --> 00:19:51,680
then you know the nice thing is is you ain't gonna worry about recovery and

245
00:19:51,680 --> 00:19:56,880
their their pressures are pressures related to temperature are very very

246
00:19:56,880 --> 00:20:01,520
close to 22 yeah I seen our very first one a lot of people missed it we had our

247
00:20:01,520 --> 00:20:10,040
very first one at the AHR show this year we had a three ton our 290 air to water

248
00:20:10,040 --> 00:20:15,520
residential heat pump three three ton three on two point eight pounds of our

249
00:20:15,520 --> 00:20:24,800
290 yeah but as the next generation that's what we have to look at so you

250
00:20:24,800 --> 00:20:29,720
know we were worried about the pressure increase when we went from 22 to 410

251
00:20:29,720 --> 00:20:35,760
we're worried about the flammability going from 410 to 32 and 454 B the next

252
00:20:35,760 --> 00:20:38,660
we're gonna probably worry about the flammability not realizing that the

253
00:20:38,660 --> 00:20:44,400
pressures are actually going way down lower when we go to 290 or 600 right and

254
00:20:44,400 --> 00:20:48,680
but it all still is going to actually maintain those similar same saturation

255
00:20:48,680 --> 00:20:52,640
design and saturation you know the only thing you'll be keeping your eye on is

256
00:20:52,640 --> 00:21:00,280
the sear rating of these and you know and of course the the lower the lower

257
00:21:00,280 --> 00:21:05,480
the condenser split the better in other words the the lower amount that we've

258
00:21:05,480 --> 00:21:08,160
got to raise that pressure to get that heat rejection the less work the

259
00:21:08,160 --> 00:21:11,480
compressors got to do let's work and that's more efficient so like I've got a

260
00:21:11,480 --> 00:21:17,880
20 sear unit and and yes it comes up to my chin just about and a whopping two

261
00:21:17,880 --> 00:21:26,040
tons and and yet it's 10 degrees over so if it's 95 outside I'm only run 105

262
00:21:26,040 --> 00:21:29,840
condensing temperature wow so you bring the pressures down even a little bit

263
00:21:29,840 --> 00:21:37,080
yeah very cool so alright easy it is easy simple math easy and simple and

264
00:21:37,080 --> 00:21:40,840
don't forget you too

265
00:21:42,600 --> 00:21:46,760
Jojo the HFAC man I appreciate you hanging out with us today and I look

266
00:21:46,760 --> 00:21:51,520
forward to some more conversations love it thank you Cliff

